NH fuse-link gG, 400VAC, size 000, 100A double indicator/insulated tags
Item #:
D223701
Product Info
NH000GG40V100
Mersen
The NH system is classified among plug-in fuse systems and is composed of , fuse-base (possibly including terminal covers and phase barriers) , fuse-link with blade contact , fuse-link replacement device (LV HRC fuse puller) Since the design of this system cannot guarantee non-interchangeability of rated current it must be handled by a qualified professional. Type "gG" NH fuse-links are full range breaking capacity fuse-links and are used to protect cables and equipment. They can interrupt any current surge, from the lowest fusing current up to their breaking capacity, and so can be used alone as protection. They also protect electrical devices and industrial set-ups from the electrodynamic effects of very high short-circuit currents. Rated Power Dissipation values of Mersen NH fuse-links 400VAC are below the maximum values required by standard IEC 60269.
0% cadmium; Lead free contact blades; Dimensions according to DIN 43 620 Parts 1 to 4; Double indicator; IEC 60269-1 and -2; Isolated metal gripping lugs (SGL); VDE 0636 Part 201
Item Specifications
-
100 A
-
100 A
-
Ceramic
-
Silver-Plated Copper
-
Hungary
-
NH000
-
Clip
-
Clip
-
5.7 W
-
NH fuse-links gG 400VAC , double indicator/isolated gripping-lugs size 000, 00, 1, 2, 3
-
400 V
-
gG
-
Silver-Plated Copper